ENC-AR2200EX-CU
Demonstrate an ability to powerful cooling at various board power inverter.
Specifications
Mount Type Roof-mount Cooling Capacity (W) 1900/2200 Setting Temperature Range (°C) 25 to 45 Use Area Temperature (°C) 20 to 55 Use Area Humidity (%RH) 10-85(No condensation) External Dimensions (mm) H447×W650×D400 Volume (kg) 48 Coating Color Color Munsell 5Y7 / 1 light beige Voltage Rating (V) Three phase AC200 Consumption Current/Rating (A) 3.3/3.2 Consumption Current/MAX (A) 4.2/4.1 Starting Current (A) 27/25 Consumption Voltage/Rating (W) 850/1050 Consumption Voltage/MAX (W) 1050/1250 Noise Resistance EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2 Vibration Resistance Equivalent to JIS Z 0200 Level1 Dust & Water Protection Grade Equivalent to IP54 (internal circulation route) Coolant / Filling (g) HFC-134a 575g Noise (dB) 70/71 External Output Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) Display LED / RUN LED display / temperature error in the panel Regulatory Compliance CE marking, Standard UL, Electrical Appliance and Material Safety Law Environmental Response RoHS