Show their ability to measure heat of outdoor power panel board and various information and communications equipment.

  • Specifications

    Mount Type Side-mount
    Cooling Capacity (W) 2600/2900
    Setting Temperature Range (°C) 25 to 45
    Use Area Temperature (°C) -5 to 55
    Use Area Humidity (%RH) 10-85(No condensation)
    External Dimensions (mm) H1380×W450×D295
    Volume (kg) 60
    Surface Finish 180-HL No.4 NSSC finish
    Voltage Rating (V) Single-phase AC200
    Consumption Current/Rating (A) 7.8/7.3
    Consumption Current/MAX (A) 9.3/9.4
    Starting Current (A) 33/30
    Consumption Voltage/Rating (W) 1300/1500
    Consumption Voltage/MAX (W) 1650/1850
    Noise Resistance Fast Transient / LEVEL4 by burst immunity test
    Vibration Resistance Equivalent to JIS Z 0200 Level1
    Dust & Water Protection Grade Equivalent to IP54 (internal circulation route)
    Coolant / Filling (g) HFC-134a 500g
    Noise (dB) 68/70
    External Output Cooling operation output, alarm output (a non-voltage contact: Resistive load 250V 2A)
    Display LED RUN LED display / temperature error in the panel
    Regulatory Compliance Electrical Appliance and Material Safety Law
    Environmental Response RoHS