1000W type of non-drain type, Demonstrate every feature on the site of production.

  • Specifications

    Mount Type Roof-mount
    Cooling Capacity (W) 1150/1300
    Setting Temperature Range (°C) 25 to 45
    Use Area Temperature (°C) 20 to 50
    Use Area Humidity (%RH) 10-85(No condensation)
    External Dimensions (mm) H448×W710×D370
    Volume (kg) 44
    Coating Color Color Munsell 5Y7 / 1 light beige
    Voltage Rating (V) Single-phase AC100
    Consumption Current/Rating (A) 7.2/7.0
    Consumption Current/MAX (A) 8.7/9.5
    Starting Current (A) 22.3/20.5
    Consumption Voltage/Rating (W) 590/680
    Consumption Voltage/MAX (W) 770/900
    Noise Resistance Fast Transient / LEVEL4 by burst immunity test
    Vibration Resistance Equivalent to JIS Z 0200 Level1
    Dust & Water Protection Grade Equivalent to IP54 (internal circulation route)
    Coolant / Filling (g) R-407c 385g
    Noise (dB) 65/68
    External Output Alarm output (a contact: No-voltage resistive load 250V 2A)
    Display LED RUN LED display / temperature error in the panel
    Regulatory Compliance EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4
    Environmental Response RoHS