ENC-G2200EX
Demonstrate a high cooling capacity in various high output inverter panel and independence panel.
Specifications
Mount Type Roof-mount Cooling Capacity (W) 1900/2200 Setting Temperature Range (°C) 25 to 45 Use Area Temperature (°C) 20 to 55 Use Area Humidity (%RH) 10-85(No condensation) External Dimensions (mm) H447×W650×D400 Volume (kg) 48 Coating Color Color Munsell 5Y7 / 1 light beige Voltage Rating (V) Three phase AC200 Consumption Current/Rating (A) 3.3/3.2 Consumption Current/MAX (A) 4.7/4.9 Starting Current (A) 27/25 Consumption Voltage/Rating (W) 850/1050 Consumption Voltage/MAX (W) 1050/1250 Noise Resistance Fast Transient / LEVEL4 by burst immunity test Vibration Resistance Equivalent to JIS Z 0200 Level1 Dust & Water Protection Grade Equivalent to IP54 (internal circulation route) Coolant / Filling (g) HFC-134a 575g Noise (dB) 70/71 External Output Alarm output (a contact: No-voltage resistive load 250V 2A) Display LED RUN LED display / temperature error in the panel Regulatory Compliance EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 Environmental Response RoHS