top of page
ENC-G2900EX

ENC-G2900EX

Large cooling capacity cooler excellent environmental resistance, the margin.

  • Specifications

    Mount Type Roof-mount
    Cooling Capacity (W) 2600/2900
    Setting Temperature Range (°C) 25 to 45
    Use Area Temperature (°C) 20 to 55
    Use Area Humidity (%RH) 10-85(No condensation)
    External Dimensions (mm) H447×W760×D400
    Volume (kg) 57
    Coating Color Color Munsell 5Y7 / 1 light beige
    Voltage Rating (V) Three phase AC200
    Consumption Current/Rating (A) 4.8/4.7
    Consumption Current/MAX (A) 7.0/7.1
    Starting Current (A) 31.0/30.0
    Consumption Voltage/Rating (W) 1270/1450
    Consumption Voltage/MAX (W) 1700/1900
    Noise Resistance Fast Transient / LEVEL4 by burst immunity test
    Vibration Resistance Equivalent to JIS Z 0200 Level1
    Dust & Water Protection Grade Equivalent to IP54 (internal circulation route)
    Coolant / Filling (g) HFC-134a 775g
    Noise (dB) 72/73
    External Output Alarm output (a contact: No-voltage resistive load 250V 2A)
    Display LED RUN LED display / temperature error in the panel
    Regulatory Compliance EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4
    Environmental Response RoHS
bottom of page