ENC-G810EXE
Vaporization unit was equipped with a drain, a revolutionary type ceiling.
Specifications
Mount Type Roof-mount Cooling Capacity (W) 700/800 Setting Temperature Range (°C) 25 to 45 Use Area Temperature (°C) 20 to 50 Use Area Humidity (%RH) 10-85(No condensation) External Dimensions (mm) H338×W670×D353 Volume (kg) 30 Coating Color Color Munsell 5Y7 / 1 light beige Voltage Rating (V) Single-phase AC100 Consumption Current/Rating (A) 5.7/4.9 Consumption Current/MAX (A) 6.6/6.5 Starting Current (A) 15.6/14.7 Consumption Voltage/Rating (W) 470/475 Consumption Voltage/MAX (W) 600/640 Noise Resistance Fast Transient / LEVEL4 by burst immunity test Vibration Resistance Equivalent to JIS Z 0200 Level1 Dust & Water Protection Grade Equivalent to IP54 (internal circulation route) Coolant / Filling (g) HFC-134a 250g Noise (dB) 60/65 External Output Alarm output (a contact: No-voltage resistive load 250V 2A) Display LED RUN LED display / temperature error in the panel Regulatory Compliance EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 Environmental Response RoHS