  • Specifications

    Mount Type Roof-mount
    Cooling Capacity (W) 1350/1500
    Setting Temperature Range (°C) 25 to 45
    Use Area Temperature (°C) 20 to 50
    Use Area Humidity (%RH) 10-85(No condensation)
    External Dimensions (mm) H478×W590×D350
    Volume (kg) 43
    Coating Color Color Munsell 5Y7 / 1 light beige
    Voltage Rating (V) Single-phase AC200 to 240
    Consumption Current/Rating (A) 2.8 / 3.5
    Consumption Current/MAX (A) 3.0 / 4.1
    Starting Current (A) 8.7 / 8.8
    Consumption Voltage/Rating (W) 575 / 715
    Consumption Voltage/MAX (W) 685 / 815
    Vibration Resistance 5Hz frequency 20mm total amplitude
    Coolant / Filling (g) R744 / 400
    Noise (dB) 67 / 67
    External Output Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A)
    Display LED RUN LED display / temperature error in the panel
    Environmental Response RoHS