top of page
PAU-A3500S-HC

PAU-A3500S-HC

High-enthalpy type that can accommodate a variety of applications.

  • Specifications

    Cooling Method Air-Cooled Type
    Type Temperature and humidity Controller
    Cooling Capacity (W) 4500/5200
    Heating Capacity (W) 7800
    Humidifying Capacity (kg/h) 15.6
    Temperature Control Precision (°C) +-0.2
    Setting Temperature Range (°C) 20~30
    Humidity Control Precision (%RH) +-1.0
    Setting Humidity Range (%RH) 40~80
    Use Area Temperature (°C) 20 ~ 35 (change in temperature gradient: within 1°C/1h)
    Use Area Humidity (%RH) 10 ~ 85 (change in temperature gradient: within 5%/1h) (No condensation)
    Processed Air Volume (m2/min)(50Hz) 21/24
    External Dimensions(mm) H1481×W650×D1115
    Volume (kg) 260
    Coating Color Ivory (JPMA: Semi-gloss Y22-85B)
    Blower Duct Connection Diameter (mm) φ200 with damper
    Rated Voltage (V) Three-phase AC200
    Consumption Current (A) 7.5/8.5(MIN) 63.2/64.6(MAX
    Wattage (W) 2000/2500(MIN) 21800/22300(MAX)
    Humidifier/Water Supply Volume (ℓ/h) 18
    Humidifier/Water Supply Pressure (MPa) 0.03-0.5
    Water Supply Temperature (°C) 0-50
    Humidifier/Water Supply Connection Diameter (mm) 15A female socket (Rc: 1/2 inch)
    Drain Discharge Water Connection Diameter (mm) 20A female socket (Rc: 3/4 inch)
    Coolant R-407c 1470g
    Exhaust Air Volume (m3/min) (Inverter control) 32.5/41.5
    Safety Circuit/Main Circuit Earth leakage circuit breaker (75A 30mA)
    Safety Circuit/Blower Overcurrent relay (manual reset) (3.3A), Delay timer (3 minutes), Surge Absorber
    Safety Circuit/Compressor Overcurrent relay, motor protectors, surge absorbers, low temperature thermostat driving prevention
    Safety Circuit/Heater Thermostat to prevent overheating (65°C OFF 55°C ON), thermal fuse (99°C), surge absorber
    Safety Circuit/Humidifier Float switch, thermostat to prevent overheating (120°C +- 10 ℃ OFF), fuse temperature (119°C), automatic timer drainage, drainage manual switch, surge absorber
    Output/Main Unit Malfunction Output No-voltage contact a (AC250V / 3A / Resistive load)
    Output/Temperature Control Top-Bottom Limit Alarm No-voltage contact a (AC250V / 3A / Resistive load)
    Output/Humidity Control Top-Bottom Limit Alarm No-voltage contact a (AC250V / 3A / Resistive load)
bottom of page